线路型避雷器阻性电流自供能监测系统

The Self-powered Monitoring System of Resistive Current for Line Type Metal Oxide Arrester

  • 摘要: 氧化锌避雷器(MOA)阻性电流可表征避雷器状态。运用基波法提取线路型避雷器阻性电流时,存在难以精准获取线路电压、监测装置供能困难等问题。为此,提出一种线路型避雷器阻性电流自供能监测系统。基于介电及静电感应理论,量化分析线路下方感应板分压电压及感应电压,设计了适用于线路型MOA的无源电压测量装置;考虑微电流特性及干扰,设计含放大滤波等功能的测量电路,实现了最低500 μA的全电流测量;根据电容充放电特性及能量守恒关系,设计微电流取能电路,500 μA电流下可供给系统超过1.1 mW的能量。14 kV电压试验验证了35 kV MOA工作于线性区时,系统可自供能运行并提取MOA的 μA级阻性电流。

     

    Abstract: The resistive current of metal oxide arrester (MOA) can be used to characterize the state of the arrester. However, it is difficult to accurately obtain the line voltage and monitor the energy supply of the device when the resistive current of the wire is extracted by the fundamental wave method. In this paper, a self-powered monitoring system for the resistive current of a wire-type arrestor is proposed. Based on the theory of dielectric and electrostatic induction, a passive voltage measurement device for the line MOA is designed by quantifying the partial and induced voltages of the induction plate below the line. Considering the microcurrent characteristics and interference, a measuring circuit with amplifying and filtering functions is designed to achieve the full current measurement with a minimum of 500 μA. According to the charge-discharge characteristics of capacitor and the energy conservation relationship, a micro-current energy extraction circuit is designed, which can supply more than 1.1 mW of energy to the system at 500 μA current. The experiments at 14 kV voltage verifies that the system can run on the extracted energy, and extract μA class resistance current of the 35 kV MOA when it operates in linear region.

     

/